Part Number Hot Search : 
CDBN0230 AD639 VRE101C MIC25 BCM73 V0DS00 C330K 5L380
Product Description
Full Text Search
 

To Download 520-K-1-01-SI1-100A Datasheet File

  If you can't view the Datasheet, Please click here to try to view without PDF Reader .  
 
 


  Datasheet File OCR Text:
  1 description typical applications interrupting capacity to iec 60947/en 60947 approvals technical data single, double and three pole high performance thermal-magnetic circuit breakers with tease-free, trip-free, snap action mechanism and toggle actuation (s-type tm cbe to en 60 934; also to en 60 947). designed for rail, panel or surface mounting. available with a choice of characteristic curves and optional auxiliary contacts. motors, generators, transformers, thyristors and silicon rectifiers. 410-... 530-... voltage rating ac 240 v; 3 ac 415 v; 3 ac 500 v dc 110 v current rating range curves 01, 02, 04, 05: 10...125 a (en 60947) curves b3, c3, 01: 7...100 a (en 60898) auxiliary circuit 6 a, ac 240 v or dc 28 v 1 a, dc 110 v typical life 10,000 operations at 1 x i n 20,000 operations mechanical ambient temperature -40...+60 c (-40...+140 f) insulation co-ordination rated impulse pollution (iec 60664 and 60664a) withstand voltage degree 6 kv 3 dielectric strength (iec 60664 and 60664a) test voltage operating area ac 3,300 v pole/pole ac 3,300 v main circuit/aux.circuit ac 2,200 v aux. circuit 11-12/13-14 ac 1,000 v insulation resistance > 100 m (dc 500 v) degree ef protection operating area ip40 (iec 60529/din 40050) terminal area ip00 vibration curves 02, 04, 05, b3, c3: 4 g (60-500 hz), 0.30 mm (10-60 hz) curve 01: 3 g (60-500 hz), 0.23 mm (10-60 hz) to iec 60068-2-6, test fc 10 frequency cycles/axis shock curves 02, 04, 05, b3, c3: 50 g (11 ms) directions 1, 2, 3, 4, 5 30 g in direction 6 curve 01: 30 g (11 ms) in directions 1, 2, 3, 4, 5 20 g in direction 6 to iec 60068-27, test ea corrosion 96 hours at 5 % salt mist, to iec 60068-2-11, test ka humidity 240 hours at 95 % rh to iec 60068-2-3, test ca mass 410 (1-pole): approx. 290 g 520 (2-pole): approx. 580 g 530 (3-pole): approx. 870 g standard current ratings and typical internal resistance values ac voltage number of poles voltage rating interrupting capacity i n power factor interrupting capacity i n power factor i n 12...125 a i n 7 + 10 a 1 ac 240 v 5,000 a cos? = 0.7 3,500 a cos? = 0.8 2 ac 240 v 8,000 a cos? = 0.7 6,000 a cos? = 0.7 3 3 ac 415 v 5,000 a cos? = 0.7 3,000 a c os? = 0.85 dc voltage number of poles voltage rating interrupting capacity i n time constant interrupting capacity i n time con- stant i n 12...125 a i n 7 + 10 a 1 dc 110 v 3,000 a 13 ms 3,000 a l/r = 5 ms 1 dc 110 v 5,000 a 5 ms 2 dc 110 v 5,000 a 13 ms 3,000 a l/r = 5 ms 2 dc 110 v 10,000 a 0 ms curves 01, 02, 04, 05: curves b3, c3: current rating (a) internal resistance () per pole current rating (a) internal resistance () per pole 10 0.033 7 0.033 16 0.015 10 0.015 20 0.010 12 0.015 25 0.0062 16 0.010 32 0.0039 20 0.0062 40 0.0031 25 0.0039 50 0.0022 32 0.0031 63 0.002 40 0.0022 80 0.002 50 0.002 90 0.002 63 0.002 100 0.002 80 0.002 125 0.002 100 0.002 authority standard rated voltage current ratings ul ul 1077 c22.2 no 235 ac 277 v 7...125 a (type 520) high performance thermal-magnetic circuit breakers 410/520/530-... www.e-t-a.de 1646 1
2 surface mounting -1 rail mounting (din en 50 022-35x7,5) -2 panel mounting -4 ordering information type no. 410 single pole (ratings > 125 a: suffix 17015 - parallel connection) 520 double pole 530 three pole terminal design - main terminals k screw terminals 10-32 a pressure plate b5-din 46288 (curves b3/c3, 7-25 a) 40-63 a pressure plate b6-din 46288 (curves b3/c3, 32-63 a) 80-125 a terminal screw din 46206, sheet 2, form 1, m6 thread mounting 1 surface mounting 2 rail mounting (din en 50022-35x7.5) or panel mounting 4 panel mounting with cylinder head screw m3.5 magnetic trip curves 01 2.1-3 x i n ac (thyristor and rectifier protection) 02 7-10 x i n ac (motor and generator protection to en 60947) 04 3.5-5 x i n ac (cable protection to en 60947) 05 4-6 x i n ac (generator protection to en 60947) b3 3-5 x i n ac (cable protection to en 60898) c3 5-10 x i n ac (cable protection to en 60898) auxiliary contacts optional (terminals m3.5) si one each n/o and n/c contact si1 one n/c (11,12) current ratings 7...125 a 520 - k - 1 - 01 - ... - 10 a ordering example the exact number required can be built up from the table of choices shown above. ordering references for optional features should be omitted if not required. mounting methods dimensions 1 1 14 66 14 66 114 44 1 4 1 4 6 4 4 tightening torque 32 a 63 a 125 a dimensions mm/in. terminal b pressure plate b6 din 46288 terminal screw 97 3.7 22 ?4.6 4. 6 14.6 surface mounting 35 ?20 ?4 22 +0,5 44 +1 monting holes 26 26 106 90.5 71.5 41 6 92 16 symmetrical rail din en 50022-35x7.5 g profile rail din en 50035-g32 (not shown) d 45 35 66 44 22 e b c si terminals m3.5 1 n/c off on type 410 type 520 m3.5 - thread max. 9 mm (.354 in.) deep tightening torque max. 0.8 n 3 pole 1 pole 2 pole 3 1 n/o current rating type 530 cross section (see din 46288) with 1 or 2 equal conductors with 2 different conductors m5 m6 m6 cd e 2.0 nm 2.5 nm 2.5 nm 2.5 mm 2 to 10 mm 2 2.5 mm 2 to 10 mm 2 4 mm 2 to 16 mm 2 4 mm 2 and 6 mm 2 or 6 mm 2 to 16 mm 2 .236 3.56 1.64 4.17 .118 2.82 3.62 .630 1.77 1.38 .866 1.73 2.60 19 .748 .575 .181 3.82 .146 .181 .866 .787 1.38 .157 .866 +.020 1.73 +.039 pressure plate b5 din 46288 this is a metric design and millimeter dimensions take precedence ( mm ) inch high performance thermal-magnetic circuit breakers 410/520/530-... www.e-t-a.de 1646 1
3 line 1 line 1 line 1 6 i > 3 i > i > 3 5 i > line 1 2 2 11 12 13 14 4 i > 2 4 i > 11 12 13 14 i > 2 11 12 13 14 type 410-k type 410-k-si type 520-k-si type 530-k-si ? times rated current trip time in second s ? times rated current trip time in seconds 12 46 8 10 20 40 10000 1000 100 10 1 0. 1 0.01 0.001 60 80 100 12 46 8 10 20 40 10000 1000 100 10 1 0.1 0.01 0.001 60 80 100 01 02 04 05 b3 c3 typical time/current characteristics at +23 c/+73.4 f internal connection diagrams shock directions 1 2 4 3 5 6 magnetic trip curves 01,02,04,05 ac/dc 1) magnetic trip curves b3,c3 ac/dc 1) 1) magnetic tripping currents are increased by 20% on dc supplies. high performance thermal-magnetic circuit breakers 410/520/530-... www.e-t-a.de 1646 1 high performance thermal-magnetic circuit breakers 410/520/530-...
4 accessories mounting hole 38 21 max. 4 1.2 24.5 44 53 40 53 62 59 35 22 ?4 38 max. 4 24.5 splash cover (transparent), with fixing plate and screws (ip54) for type 410 x 211 118 01 splash cover (transparent), with fixing plate and screws (ip54) for type 520 x 211 119 01 59 +0.3 2.09 2.44 25 +0.3 .984 +.012 2.32 +.012 .157 max .157 .965 .965 1.50 .827 .047 2.32 .866 1.38 2.09 max .157 21 1. 2 .827 .047 25 +0.3 .984 +.012 35 ?4 .157 mounting hole 1.38 40 +0.3 1.57 +.012 1.50 1.57 1.73 165 ?10 44 64 19 92 94 protected against brush contact * * to din 57106t100/vde 0106 t100 6.50 .748 2.52 3.62 3.70 .394 1.73 terminal insulation cover for 410/520/530-... x 211 705 01 (1 set = 2 pcs per pole) this is a metric design and millimeter dimensions take precedence ( mm ) inch all dimensions without tolerances are for reference only. in the interest of improved design, performance and cost effectiveness the right to make changes in these specifications without notice is reserved.product markings may not be exactly as the ordering codes. errors and omissions excepted. high performance thermal-magnetic circuit breakers 410/520/530-... www.e-t-a.de 1646 1


▲Up To Search▲   

 
Price & Availability of 520-K-1-01-SI1-100A

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .